Gas water heater in the garage
What's wrong here?
- The burner and ignition source must be at least 18 in. above the garage floor
- The relief valve discharge must be piped through the wall to the outdoors
- A gas water heater may not be installed in a garage
- Nothing. This installation is compliant
Show the answer and the code reference
The answer
Nothing is wrong. The heater is FVIR-listed, so it can sit on the garage floor, and the bollard keeps the car off it.
Correct choice: 4. Nothing. This installation is compliant
The 18 in. rule exists because gasoline vapor is heavier than air and pools near a garage floor, where a standing pilot or burner can ignite it. UPC 507.13 requires burners and ignition devices in a residential garage to be at least 18 in. above the floor unless the appliance is listed as flammable vapor ignition resistant. Gas storage water heaters built since the mid-2000s are generally FVIR-listed (their combustion chambers are sealed with a flame-arresting air intake), and this one is labeled. UPC 507.13.1 also requires protection from vehicle damage by a barrier, elevation or location out of the vehicle path; here a concrete-filled bollard does that. The rest checks out: shutoff on the cold, an expansion tank on the cold line, a sediment trap on the gas, and a full-size relief discharge ending near the slab.
How to fix it
No correction needed. On an older heater with no FVIR listing, the same spot would need a stand that puts the burner and ignition source at least 18 in. above the slab.
Code references
UPC 2018 507.13 — Installation in Garages
Appliances in residential garages, and in adjacent spaces that open to the garage and are not part of the living space, shall be installed so that burners and burner-ignition devices are at least 18 in. above the floor, unless listed as flammable vapor ignition resistant.
Drills citing 507.13UPC 2018 507.13.1 — Physical Damage
Appliances in garages and other areas subject to mechanical damage shall be guarded against it by protective barriers, by elevation, or by being located out of the normal path of vehicles.
Drills citing 507.13.1Other IFGC 2018 305.3 — Elevation of ignition source (Minnesota Fuel Gas Code)
Appliances with an ignition source in private garages and similar locations shall have the ignition source at least 18 in. above the floor; an exception exempts appliances listed as flammable vapor ignition resistant. Minnesota adopts the 2018 IFGC with amendments as the Minnesota Fuel Gas Code (Minn. Rules ch. 1346).
Drills citing IFGC 2018 305.3UPC 2018 608.5 — Discharge Piping
Relief valve discharge piping is full size, has no valves, traps or threaded end, and discharges by gravity through an air gap. The model code sends it into the drainage system or outside the building; Minnesota's amendment (Minn. Rules 4714.0608) is reported to let it terminate at a safe place of disposal or within 18 in. of the floor.
Drills citing 608.5
Minnesota
Minnesota deletes large parts of UPC section 507 because fuel-gas appliance installation is covered by the Minnesota Fuel Gas Code (Minn. Rules ch. 1346, the 2018 IFGC with amendments); search results indicate 507.13 is not among the deleted subsections, but that was not confirmed. The Fuel Gas Code's 305.3 carries the same 18 in. rule and the same FVIR exception, so the answer holds either way.
About the Minnesota Plumbing CodeCitation under review. This answer depends on Minnesota’s change to UPC 608.5 (Minn. Rules 4714.0608), not yet checked against the rule text. Ask your inspector.
Why the other choices are wrong
- The burner and ignition source must be at least 18 in. above the garage floor. UPC 507.13 (and fuel gas code 305.3) waive the 18 in. elevation for appliances listed as flammable vapor ignition resistant. The FVIR label shows this heater is, so it may sit on the slab.
- The relief valve discharge must be piped through the wall to the outdoors. Minnesota amends 608.5 to let the discharge end at a safe place of disposal or within 18 in. of the floor instead of outdoors or in a drain, and this full-size, unthreaded pipe ends about 6 in. above the slab. A line run out through a Minnesota garage wall would also risk freezing, which 608.5 prohibits.
- A gas water heater may not be installed in a garage. No code bans them. UPC 507.13 sets the conditions: an elevated or FVIR-listed ignition source, plus protection from vehicles under 507.13.1, which the bollard provides.