FramingWalls & headersLevel 22018 IRC

Laundry room partition with door opening

New 2x4 partition in a finished-basement laundry area, seen from the hallway side before drywall. A floor joist runs lengthwise directly above the wall, its long side facing the camera, and the next joists over run the same way. The wall has a single top plate and a green-tinted treated bottom plate on the slab. A door rough opening about 3 ft wide has a king and a jack stud on each side and a single 2x4 laid flat across the top, with two short cripples up to the top plate. To the right a recessed washer outlet box with red and blue valves and a PVC standpipe sits between studs, with PEX lines dropping through the top plate, and an orange cable is stapled down a stud to a blue dryer receptacle box. Red fire caulk seals the holes where the PEX and cable pass through the top plate. A utility sink and a floor drain are visible in the laundry room beyond. SPF No.2S-DRY 2x10
Finished-basement laundry room partition, hallway side, ready for drywall inspection

What's wrong here?

  1. Table R602.7.5 requires two full-height king studs at each side of this opening
  2. Every stud wall must be capped with a double top plate
  3. A single flat 2x4 may not be used as a header over a door opening
  4. Nothing. This installation is compliant
Start this drill
Show the answer and the code reference

The answer

Nothing is wrong: this is an interior nonbearing partition, so a single flat 2x4 header and a single top plate are both permitted.

Correct choice: 4. Nothing. This installation is compliant

The floor joist above runs parallel to the partition, so no joists, rafters or trusses bear on it; the wall only holds up itself and the drywall. R602.7.4 says load-bearing headers are not required in nonbearing walls and allows a single flat 2x4 header for openings up to 8 ft wide where the vertical distance to the parallel nailing surface above is no more than 24 in., which is easily met here. R602.5 lets interior nonbearing walls be capped with a single top plate (and even framed with 2x3 studs at 24 in. on center). The bottom plate on the basement slab is preservative-treated, the usual way to meet R317.1 for a plate resting on a slab.

How to fix it

No correction needed. Before calling it nonbearing on a real job, confirm what is above: joists running parallel to the wall, or trusses designed to clear-span, with no point loads or posts landing on the plate.

Code references

  • IRC 2018 R602.7.4 — Nonbearing walls

    Load-bearing headers are not required in interior or exterior nonbearing walls. A single flat 2x4 may be used as a header in a nonbearing wall for openings up to 8 ft wide if the vertical distance to the parallel nailing surface above is not more than 24 in.; no cripples or blocking are required above it.

    Drills citing R602.7.4
  • IRC 2018 R602.5 — Interior nonbearing walls

    Interior nonbearing walls may be framed with 2x3 studs at 24 in. on center (or flat 2x4s at 16 in. where not part of a braced wall line) and must be capped with not less than a single top plate; they must be fireblocked per R602.8.

    Drills citing R602.5

2024 IRC:not yet checked Confidence: low

Minnesota

MN adopts this rule as writtenConfidence: medium

No Minnesota amendment to R602.7.4 or R602.5 is known. DLI is adopting the 2024 IRC as the next edition; see the 2024 IRC note.

About the Minnesota Residential Code

Why the other choices are wrong

  • Table R602.7.5 requires two full-height king studs at each side of this opening. Table R602.7.5 sets the number of full-height studs at the ends of headers in exterior walls. This is an interior nonbearing partition, and one king stud each side is normal.
  • Every stud wall must be capped with a double top plate. R602.3.2's double top plate applies to exterior walls and, through R602.4, to interior bearing walls. R602.5 lets interior nonbearing walls be capped with a single top plate.
  • A single flat 2x4 may not be used as a header over a door opening. R602.7.4 allows a single flat 2x4 header in a nonbearing wall for openings up to 8 ft wide when the nailing surface above is no more than 24 in. away. The joist above runs parallel to this partition, so nothing bears on it.
Code complianceLevel 2 · Journeyman#nonbearing#partition#flat header#top plate#laundry#calibration